200A Loadbreak Bushing Insert

200A Loadbreak Bushing Insert
WADT 15/200
Used with loadbreak connectors meeting the requirements of IEEE 386,Figure 5 Compact design Manufactured from high quality EPDM rubber.
Technical Data

Item | Bushing Insert |
Rated Voltage(U0/U) | 8.3/14.4kV |
Rated Current | 200A |
AC Withstand Voltage | 34kV for 1min |
Partial Discharge | 11kV,≤3pC |
Impulse Withstand Voltage(10 times for each polarity) |
95kV |
Tape Specification
Features
​ Used with loadbreak connectors meeting the requirements of IEEE 386,Figure 5
Compact design
Manufactured from high quality EPDM rubber.