6181XY - BS 7889
6181XY - BS 7889 Cross

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 7889.

Technical Data

Voltage Rating: 1.5 mm² to 630 mm² – 600 / 1000V

Harmonised Designation : -15 °C to 90°C

Minimum Bending Radius:

4.0 to 50 mm²: 10 X Overall diameter

70 & 630 mm²: 12 X Overall diameter

Test Voltage: 2 kV 15 min.

Cabel Design Parameters

Part Number Nominal Cross
Sectional Area
(sq, mm)
Nominal
Insulation Thickness (mm)
Nominal Sheath
Thickness
(mm)
Approx. Overal Diameter (mm) Approx. Net
Weight (kg/km)
11600100004 4 0.70 1.40 8.0 107
11600100006 6 0.70 1.40 8.5 132
11600100010 10 0.70 1.40 9.5 181
11600100016 16 0.70 1.40 10.5 247
11600100025 25 0.90 1.40 12.0 358
11600100035 35 0.90 1.40 13.0 466
11600100050 50 1.00 1.40 14.0 545
11600100070 70 1.10 1.40 16.0 765
11600100095 95 1.10 1.50 18.0 1022
11600100120 120 1.20 1.50 20.0 1267
11600100150 150 1.40 1.60 22.0 1556
11600100185 185 1.60 1.60 24.0 1928
11600100240 240 1.70 1.70 27.0 2501
11600100300 300 1.80 1.80 29.0 3108
11600100400 400 2.00 1.90 32.0 3923
11600100500 500 2.20 2.00 36.0 4999
11600100630 630 2.40 2.20 40.0 6414
  • For current ratings refer table no. 9-1, for voltage drop refer table no. 9-2.