6181Y – BS 6004

6181Y – BS 6004

  • REACH
  • RoHS
  • CE
  • CPR Compliant
6181Y - BS 6004
6181Y - BS 6004 cross

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 6004:2012, EN 50363-3 with BS 7655-4.2 (Only for sheath)

Technical Data

Voltage Rating: 1.5 mm² to 35 mm² – 300 / 500V

Harmonised Designation: -15°C to 70 °C

Minimum Bending Radius:

Upto 10 mm²: 10 X Overall Diameter

16 & 35 mm²: 12 X Overall Diameter

16 & 35 mm²: 12 X Overall Diameter.

Test Voltage: 2 kV for 15 min

Construction

Conductor : Plain annealed copper conductor : 1.5 & 2.5 mm² Class -1, 4.0 to 35 mm² stranded Class 2 complying with BS EN 60228, HD 383, IEC 60228

Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3

Sheath : PVC (Polyvinyl Chloride ) compound type Type 6 complying with BS 7655-4.2

Insulation Colours : Blue and brown

Sheath Colou : Grey RAL 7001

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown.

Part Number Nominal Cross
Sectional Area
(Sq. mm)
Nominal
Insulation
Thickness (mm)
Nominal Sheath
Thickness
(mm)
Overall Diameter
Lower Limit
(mm)
Overall Diameter
Upper Limit
(mm)
Approx. Net
Weight (kg/km)
01150101xx10 1.5 0.70 0.8 4.20 5.00 37
01150102xx10 2.5 0.80 0.8 4.80 5.70 51
01150103xx10 4 0.80 0.9 5.50 6.70 75
01150104xx10 6 0.80 0.9 6.00 7.30 98
01150105xx10 10 1.00 0.9 7.30 8.80 152
01150106xx10 16 1.00 1.0 8.40 10.10 220
01150107xx10 25 1.20 1.1 10.00 12.10 336
01150108xx10 35 1.20 1.1 11.10 13.50 353
  • For current ratings refer table no. 10-1, for voltage drop refer table no. 10-2.

*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)