Description
Application
High temperature, flame retardant cable designed for use in switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
Standard
-
Adapted to BS 6862
Voltage Rating
- Max. 200V
Test Voltage
- 1000 Volts
Temperature Range
-
-40°C to + 90°C
Cable Construction
-
Bare copper strands as per EN 60228, class 6
Packing
-
Available in wooden drums.
Conductor Bunch Variants
- Normal flex and Super flex
- Special Elastomeric Insulation
- Thermoplastic Elastomer Vulcanizate
Special Properties
- Acid Resistance Test: In sulphuric acid of specific gravity 1.28 at a temperature of 160°C to 210°C and check the cable after 60 hrs.
- No effect on insulation. Insulation free from deformation and shrinkage
- Chemical Resistance: Resistant to ozone, acids, solvents, detergents, vaseline and oils.
Cable Design Parameters
| Nominal Cross-Section (mm²) | No. of Strands | Max. Strand Diameter (mm) | Outer Diameter (max.) (mm) | Max. DC Conductor Resistance at 20°C (Ω/km) |
|---|---|---|---|---|
| 25 | 784 | 0.20 | 11.1 | 0.78 |
| 35 | 1176 | 0.20 | 12.8 | 0.554 |
| 50 | 1568 | 0.20 | 14.0 | 0.386 |
| 70 | 2205 | 0.20 | 16.0 | 0.272 |
| 95 | 2989 | 0.20 | 18.0 | 0.206 |
| 120 | 3850 | 0.20 | 20.3 | 0.161 |
Normal Flex Cable
| Nominal Cross-Section (mm²) | No. of Strands | Max. Strand Diameter (mm) | Outer Diameter (max.) (mm) | Max. DC Conductor Resistance at 20°C (Ω/km) |
|---|---|---|---|---|
| 25 | 816 | 0.20 | 11.1 | 0.78 |
| 35 | 1144 | 0.20 | 12.8 | 0.554 |
| 50 | 1662 | 0.20 | 14.0 | 0.386 |
| 70 | 2346 | 0.20 | 16.0 | 0.272 |
| 95 | 3050 | 0.20 | 18.0 | 0.206 |