FR HSF

Description

FR (Flame Retardant) insulation 70°C | Hazardous substance free | Does not propagate flame & fire.

Application

Flexible single core cable with Flame Retardant PVC insulation. This cable can be used in panels, cabinets, machines and internal wirings with switchgears, relays, controllers, equipments, controls units, etc.

Technical Data

  • Approvals: IS 694 marked, FIA/TAC
  • Cable Code: Y (FR)
  • Voltage Grade: Up to and including 1100V
  • Conductor: Flexible electrolytic annealed plain copper, class 5, IS 8130
  • Insulation: FR (Flame Retardant) PVC, IS 5831
  • Packing: 200 mtr. In polybag packing or 180 mtr. coil packed in protective cartons

Properties

  • Temperature range: -15°C to +70°C
  • Max. short circuit temperature rating: 160°C
  • Self-extinguishing and flame retardant according to IS 10810 P – 61
  • Free from 200+ hazardous substance (REACH Compliant)
Part Number Nominal Cross Sectional Area (sq. mm) No of Strands / Max. strand dia. (mm) Nominal Insulation Thickness (mm) Maximum Diameter Over Insulation (mm) Max. Current Carrying Capacity (A)
020901010120 0.5 16/0.2 0.6 2.6 5
020901020220 0.75 24/0.2 0.6 2.8 8
020901030320 1 32/0.2 0.6 3.0 13
020901040420 1.5 30/0.25 0.7 3.4 17
020901050520 2.5 50/0.25 0.8 4.1 24
020901060620 4 56/0.30 0.8 4.8 30
020901070720 6 84/0.30 0.8 5.3 38
020901080820 10 140/0.30 1.0 7.0 52
020901090920 16 126/0.40 1.0 8.1 70
020901101020 25 196/0.40 1.2 10.2 88
020901111120 35 276/0.40 1.2 11.7 112
020901121220 50 396/0.40 1.4 13.9 146
020901131320 70 360/0.50 1.4 16.0 216
020901141420 95 480/0.50 1.6 18.2 262
020901151520 120 608/0.50 1.6 20.2 310
020901161620 150 750/0.50 1.8 22.5 355
020901171720 185 931/0.50 2.0 24.9 415
020901181820 240 1200/0.50 2.2 28.4 500
020901191920 300 1500/0.50 2.4 31.0 550

Test Parameters

Test Test Method Values
Limited Oxygen Index IS 10810 P-58 > 29%
Limited Temperature Index IS 10810 P-64 ≥ 250 °C
Cart (0 items)