Description
Low Smoke Zero Halogen Cable | LSZH Cable
Application
The cables are suitable for conduit wiring, especially in installations where fire, smoke, and toxic fumes create a potential threat.
Standard
BS EN 50525-3-41.
Technical Data
- Voltage Rating: Uo / U – 450 / 750V
- Harmonised Designation: 1.5 mm² to 630 mm² stranded class 2 – H07Z-R
- Temperature Range: -15°C to 90°C
- Minimum Bending Radius:
Up to 10 mm² : 3 × Overall Diameter.
16 & 25 mm² : 4 × Overall Diameter.
Above 25 mm² : 5 × Overall Diameter.
Cable Construction
- Conductor: Plain annealed copper conductor 1.5 mm² to 630 mm² stranded Cl. 2 complying with EN 60228.
- Insulation: LSZH (Low Smoke Zero Halogen) Type EI5 according to BS EN 50363-5.
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
02 – Black
03 – Red
04 – Blue
05 – Yellow
06 – Green / Yellow
07 – White
08 – Violet
09 – Brown
10 – Orange
11 – Pink
12 – Grey
| Part Number | Nominal Cross Sectional Area (sq. mm) | Nominal Insulation Thickness (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approx. Net Weight (kg/km) |
|---|---|---|---|---|---|
| 01130101xx60 | 1.5 | 0.70 | 2.70 | 3.40 | 19 |
| 01130102xx60 | 2.5 | 0.80 | 3.30 | 4.10 | 33 |
| 01130103xx60 | 4 | 0.80 | 3.80 | 4.70 | 50 |
| 01130104xx60 | 6 | 0.80 | 4.30 | 5.40 | 74 |
| 01130105xx60 | 10 | 1.00 | 5.60 | 7.00 | 126 |
| 01130106xx60 | 16 | 1.00 | 6.40 | 8.00 | 184 |
| 01130107xx60 | 25 | 1.20 | 8.10 | 10.10 | 295 |
| 01130108xx60 | 35 | 1.20 | 9.00 | 11.30 | 375 |
| 01130109xx60 | 50 | 1.40 | 10.60 | 13.20 | 510 |
| 01130110xx60 | 70 | 1.40 | 12.10 | 15.10 | 710 |
| 01130111xx60 | 95 | 1.60 | 14.10 | 17.60 | 950 |
| 01130112xx60 | 120 | 1.60 | 15.60 | 19.40 | 1240 |
| 01130113xx60 | 150 | 1.80 | 17.30 | 21.60 | 1530 |
| 01130114xx60 | 185 | 2.00 | 19.30 | 24.10 | 1800 |
| 01130115xx60 | 240 | 2.20 | 22.00 | 27.50 | 2500 |
| 01130116xx60 | 300 | 2.40 | 24.50 | 30.60 | 2990 |
| 01130117xx60 | 400 | 2.60 | 27.50 | 34.30 | 3860 |
| 01130118xx60 | 500 | 2.80 | 30.50 | 38.20 | 4900 |
| 01130119xx60 | 630 | 2.80 | 34.00 | 42.50 | 6370 |
For current ratings refer Table No. 9-1 & voltage drop refer Table No. 9-2.
*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in materials used in construction. This applies to all products intended to be permanently incorporated in construction.