Description
Application
High temperature, flame retardant cable designed for use in switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
Voltage Rating
- Max. 200V
Test Voltage
- 1000 Volts
Temperature Range
- -30°C to +70°C
Cable Construction
- Annealed Bare copper strands
- For PVC battery cable – Cl. 5 to EN 60228
- For Flexible PVC battery cable – Cl. 6 to EN 60228
- PVC insulation over bunched conductor
Packing
- Available in wooden drums.
Cable Design Parameters
Standard Battery Cable
| Nominal Cross-Section (mm²) | No. of Strands | Max. Strand Diameter (mm) | Outer Diameter (max.) (mm) | Max. DC Conductor Resistance at 20°C (Ω/km) |
|---|---|---|---|---|
| 25 | 196 | 0.40 | 9.7 | 0.780 |
| 35 | 276 | 0.40 | 12.2 | 0.554 |
| 50 | 396 | 0.40 | 13.3 | 0.386 |
| 70 | 360 | 0.50 | 14.6 | 0.272 |
Flexible Battery Cable
| Nominal Cross-Section (mm²) | No. of Strands | Max. Strand Diameter (mm) | Outer Diameter (max.) (mm) | Max. DC Conductor Resistance at 20°C (Ω/km) |
|---|---|---|---|---|
| 16 | 512 | 0.20 | 8.3 | 1.21 |
| 25 | 800 | 0.20 | 10.1 | 0.780 |
| 35 | 1120 | 0.20 | 11.8 | 0.554 |
| 50 | 705 | 0.30 | 13.3 | 0.386 |
| 70 | 990 | 0.30 | 15.5 | 0.272 |
| 95 | 1340 | 0.30 | 17.9 | 0.206 |
| 120 | 1690 | 0.30 | 19.7 | 0.161 |