Description :- India’s 1st REACH and RoHS Compliant Cable | Heat Resistant and Flame Retardant Cable.
Application :- Suitable for wiring in all types of residential and commercial infrastructure, where fire and electrical safety is utmost important.
Technical Data :-
- Approvals : IS 694 marked, FIA/TAC
- Voltage Grade : Up to and including 1100V
- Conductor : Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility. The strands are twisted with high precision to impart circularity for the conductor.
- Insulation : Specially formulated heat resistant & flame retardant PVC insulation is used. The HR FR property retards the propagation of flame without compromising safety.
- Insulation Conformity : IS 5831, Type C – HR 85°C + FR
- Colours : Red, yellow, blue, black, green, grey & white
- Marking : The cables are printed with marking of ‘GUARDEX HR FR’ upto 4 Sq. mm & "RR KABEL HR FR" for size 6 Sq. mm and onwards
- Packing : 90 mtr. coil is packed in protective cartons. Project packing of 180 mtr. also available.
Cable Design Parameters :- Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – grey, 07 – white.
Part Number |
Nominal Cross Sectional Area (Sq. mm) |
Nominal Insulation Thickness (mm) |
Number *Nominal Dia. of Strands |
Approx. Overall Diameter (mm) |
Max. DC Conductor Resistance at 20°C (Ω/km) |
Current Rating (Amps) |
Casing |
Concealed |
01010101xxy0 |
0.5 |
0.6 |
16/0.2 |
2.1 |
39.0 |
5 |
4 |
01010102xxy0 |
0.75 |
0.6 |
24/0.2 |
2.3 |
26.0 |
9 |
8 |
01010103xxy0 |
1 |
0.7 |
14/0.3 |
2.7 |
18.1 |
14 |
13 |
01010104xxy0 |
1.5 |
0.7 |
22/0.3 |
3.0 |
12.1 |
18 |
16 |
01010105xxy0 |
2.5 |
0.8 |
36/0.3 |
3.7 |
7.41 |
24 |
20 |
01010106xxy0 |
4 |
0.8 |
56/0.3 |
4.1 |
4.95 |
30 |
26 |
01010107xxy0 |
6 |
0.8 |
84/0.3 |
4.6 |
3.30 |
38 |
33 |
01010108xxy0 |
10 |
1.0 |
140/0.3 |
7.0 |
1.91 |
52 |
45 |
01010109xxy0 |
16 |
1.0 |
126/0.4 |
8.1 |
1.21 |
70 |
60 |
Cable Design Parameters :-
Test |
Test Method |
Values |
Limited Oxygen Index |
IS 10810 P-58 |
> 29% |
Limited Temp. Index |
IS 10810 P-64 |
> 250°C |