Halogen-Free H07Z-R-6491B

Halogen-Free H07Z-R-6491B

Enquire on WhatsApp

Description

Low Smoke Zero Halogen Cable | LSZH Cable

Application

The cables are suitable for conduit wiring, especially in installations where fire, smoke, and toxic fumes create a potential threat.

Standard

BS EN 50525-3-41.

Technical Data

  • Voltage Rating: Uo / U – 450 / 750V
  • Harmonised Designation: 1.5 mm² to 630 mm² stranded class 2 – H07Z-R
  • Temperature Range: -15°C to 90°C
  • Minimum Bending Radius:
    Up to 10 mm² : 3 × Overall Diameter.
    16 & 25 mm² : 4 × Overall Diameter.
    Above 25 mm² : 5 × Overall Diameter.

Cable Construction

  • Conductor: Plain annealed copper conductor 1.5 mm² to 630 mm² stranded Cl. 2 complying with EN 60228.
  • Insulation: LSZH (Low Smoke Zero Halogen) Type EI5 according to BS EN 50363-5.

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:

02 – Black

03 – Red

04 – Blue

05 – Yellow

06 – Green / Yellow

07 – White

08 – Violet

09 – Brown

10 – Orange

11 – Pink

12 – Grey

Part Number Nominal Cross Sectional Area (sq. mm) Nominal Insulation Thickness (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approx. Net Weight (kg/km)
01130101xx60 1.5 0.70 2.70 3.40 19
01130102xx60 2.5 0.80 3.30 4.10 33
01130103xx60 4 0.80 3.80 4.70 50
01130104xx60 6 0.80 4.30 5.40 74
01130105xx60 10 1.00 5.60 7.00 126
01130106xx60 16 1.00 6.40 8.00 184
01130107xx60 25 1.20 8.10 10.10 295
01130108xx60 35 1.20 9.00 11.30 375
01130109xx60 50 1.40 10.60 13.20 510
01130110xx60 70 1.40 12.10 15.10 710
01130111xx60 95 1.60 14.10 17.60 950
01130112xx60 120 1.60 15.60 19.40 1240
01130113xx60 150 1.80 17.30 21.60 1530
01130114xx60 185 2.00 19.30 24.10 1800
01130115xx60 240 2.20 22.00 27.50 2500
01130116xx60 300 2.40 24.50 30.60 2990
01130117xx60 400 2.60 27.50 34.30 3860
01130118xx60 500 2.80 30.50 38.20 4900
01130119xx60 630 2.80 34.00 42.50 6370

For current ratings refer Table No. 9-1 & voltage drop refer Table No. 9-2.

*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in materials used in construction. This applies to all products intended to be permanently incorporated in construction.