Our Products

H05Z-K & H07Z-K

Application :-
  • Halogen-free single-core wires are used for installation in dry environments for wiring up lighting fixtures and units where valuable assets are to protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts. The direct operating voltages is permitted up to 900 V against ground when they are used in rail-coaches. For the inner wiring of switch boards and distributors are to be used with an alternating nominal voltage up to 1000V or a direct voltage up to 750V against ground.
Standard :-
  • BS EN 50525-3-41.
Technical Data :-
  • Nominal Voltage : H05Z-K U / U 300 / 500V, H07Z-K U / U 450 / 750V O O
  • Harmonised Designation : 0.5 mm2 to 1 mm2 – H05Z-K, 1.5 mm2 to 240 mm2 – H07Z-K
  • Temperature Range : -15°C to +90°C
  • Minimum Bending Radius : Cable diameter ≤ 8 mm : 4 x outer diameter, Approx. diameter > 8 to 12 mm : 5 x outer diameter, Approx. diameter > 12 mm : 6 x outer diameter
  • Test Voltage : 2500V
Cable Construction :-
  • Conductor Class 5 flexible plain/metal coated stranded according to EN 60228. Insulation Polyolefin cross linked EI5 to EN 50363-5.
Tests :-
  • Smoke density to acc. to EN 61034-2.
  • Halogen free acc. to EN 50525-1, EN 60754-1.
  • Corrosivity acc. to EN 60754-2 Ozone resistant according to EN 60811-2-1.
  • Self-extinguishing and flame retardant according to EN 60332-1-2.
  • LSOH = Low Smoke Zero Halogen-Free.
Cable Design Parameters :-
  • Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.
  • By adding the suffix (in place of ‘c’) for the conductor type required: 0 = Annealed Bare Copper (ABC), 1 = Annealed Tinned Copper (ATC)
Nominal Cross Sectional Area (Sq. mm)Nominal Thickness of Insulation (mm)Mean Overall DiameterApprox. Cable Weight (kg/km)
Lower Limit (mm)Upper Limit (mm)
H05V2K-02040101xx6c0.50.61.92.49
02040102xx6c0.750.62.12.612
02040103xx6c10.62.12.815
H07V2K-02040104xx6c1.50.72.83.521
02040105xx6c2.50.83.44.333
02040106xx6c40.83.94.947
02040107xx6c60.84.45.566
02040108xx6c101.05.77.1112
02040109xx6c161.06.78.4169
02040110xx6c251.28.410.6260
02040111xx6c351.29.712.1358
02040112xx6c501.411.514.4509
02040113xx6c701.413.216.61701
02040114xx6c951.615.118.8925
02040115xx6c1201.616.720.91168
02040116xx6c1501.818.623.31456
02040117xx6c1852.020.625.81773
02040118xx6c2402.223.529.42329

Our All Leading Brands Under One Roof