FIRE ALARM CABLES

Applications :-
  • These cables are used in high rise buildings, commercial complexes, schools and educational institutions, hospitals, etc. for the connection with security systems like smoke detectors, emergency lightings, exit signboards and fire command center. These cables are used where the fire safety is utmost important.
Standard :-
  • BS 7629, BS 6387, BS 50200.
Specifications :-
  • Voltage Rating : 300/500V
  • Temperature Range : -30°C to + 70°C (The cable should not be flexed when either the ambient or cable temperature is below 0°C)
  • Minimum Bending Radius : 6D
Cable Construction :-
  • Plain annealed copper conductor to Cl. 2, BS EN 60288.
  • Primary insulation of glass mica fire resistant tape.
  • Secondary insulation of highper for mance Silicone rubber.
  • EI2 to BS7655Section 1.1.
  • Core colours : 2 Core : blue, brown., 3 Core : blue, brown, black., 4 Core : blue, brown, black, grey.
  • Earth/Drain wire of annealed tinned copper to BS EN 60228.
  • Glass fiber tape.
  • Electrostatic screen of aluminium fire barrier with 125 % overlap.
  • Sheath type LTS3 to BS 7655 section 6.1.
Cable Design Parameters :-
  • Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required as per the list: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.
Part NumberNo. of Cores & Nominal Cross Section Area (Sq. mm)No. of Strands / Strand Diameter (mm)Nominal Overall Diameter (mm)
1001002011052 x 1.57/0.539.5
1001002012052 x 2.57/0.6711.0
1001003011053 x 1.57/0.5310.1
1001003012053 x 2.57/0.6711.9
1001004011054 x 1.57/0.5311.1
1001004012054 x 2.57/0.6713.0