FIRE SURVIVAL CABLE

Applications :-
  • These cables offer the advantages of an armoured 600/1000V rated, zero halogen, low smoke cable with circuit integrity. They are intended for use in installations where vital circuits are required to continue operation in the event of the outbreak of fire. It is particularly suited for use in public buildings and constructions (such as hospitals, theatres, shopping developments, tunnels, mass transit railways, oil & petrochemical plants, power stations and computer installations) where the danger to life, equipment and structures may be greatly increased in the event of a power failure due to fire.
Standard :-
  • BS 7846
Specifications :-
  • Voltage Rating : 600 / 1000V
  • Temperature Range : -40°C to + 90°C (The cable should not be flexed when either the ambient or cable temperature is below 0°C)
  • Minimum Bending Radius : 12x overall diameter of cable
Cable Construction :-
  • Construction : Plain annealed stranded copper conductors.
  • Conductor : For sizes up to and including 16mm² are offered in circular. Shaped conductors are offered from 25 mm² and onwards.
  • Insulation : Mica (fire – resistant) tapes, covered by an extruded layer of cross – linked polyethylene.
  • Bedding : An extruded layer of thermoplastic zero halogen, low smoke compound.
  • Armour :Single layer of galvanized steel wires.
  • Sheath : Thermoplastic zero halogen, low smoke, compound.
  • Zero halogen, low Smoke cable with standard copper conductors.
Cable Design Parameters :-
  • Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required as per the list: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.
Part NumberNominal Cross Sectional Area (Sq. mm)Insulation Thickness (mm)Nominal Armour Wire Diameter (mm)Approx. Diameter Under Armour (mm)Approx. Overall Diameter (mm)Approx. Cable Weight (kg/km)Max. DC Conductor Resistance at 20°C (O/km)Max. AC Conductor Resistance at 90°C (O/km)Reactance at 50Hz (O/km)AC Impedance at 90°C (O/km)Max. Arm. Resistance at 20°C (O/km)
2 Core1003002011051.5*0.60.98.513.041512.115.4280.10415.42810.7
1003002011051.5*0.60.98.513.041512.115.4280.104 15.42810.7
1003002012052.5*0.70.910.014.54957.419.4480.101 9.4488.8
1003002000044*0.70.911.015.55754.615.8780.099 5.8787.9
1003002000066*0.70.912.517.06583.083.9270.094 3.9287
10030020001010*0.70.914.019.08281.832.3330.093 2.3356
100300200016160.71.2516.021.510051.151.4660.088 1.4693.8
100300200025250.91.2515.521.211050.7270.9270.082 0.933.7
100300200035350.91.617.524.015550.5240.6680.077 0.6732.5
100300200050501.01.620.026.518550.3870.4940.076 0.52.3
100300200070701.11.623.030.024550.2680.3420.075 0.3492
100300200095951.12.026.034.033450.1930.2470.074 0.2581.4
1003002001201201.22.029.037.038980.1530.1960.072 0.2091.3
1003002001501501.42.032.040.046450.1240.160.073 0.1761.2
1003002001851851.62.536.045.559450.09910.1280.073 0.1480.82
1003002002402401.72.540.050.073450.07540.0990.072 0.1220.73
1003002003003001.82.544.054.586950.06010.080.072 0.1070.67
1003002004004002.02.549.560.0107450.0470.0640.071 0.0960.59
3 Core1003003011051.5*0.60.99.013.542312.115.4280.10415.42810.2
1003003011051.5*0.60.99.013.542312.115.4280.104 15.42810.2
1003003012052.5*0.70.910.515.05447419.4480.101 9.4488.2
1003003000044*0.70.911.516.56444.615.8780.099 5.8787.5
1003003000066*0.70.913.017.57383.083.9270.094 3.9256.6
10030030001010″0.71.2515.020.510851.832.3330.093 2.3354
100300300016160.71.2517.022.513131.151.4660.088 1.4693.6
100300300025250.91.620.026.518030.7270.9270.082 0.932.5
100300300035350.91.622.029.022020.5240.6680.077 0.6732.3
100300300050501.01.622.529.524530.3870.4940.076 0.52
100300300070701.11.626.033.032020.2680.3420.075 0.3491.8
100300300095951.12.030.038.044550.1930.2470.074 0.2581.3
1003003001201201.22.033.041.553050.1530.1960.072 0.2091.2
1003003001501501.42.537.046.567050.1240.160.073 0.1760.78
1003003001851851.62.541.051.080520.09910.1280.073 0.1480.71
1003003002402401.72.546.056.099530.07540.0990.072 0.1220.63
1003003003003001.82.551.061.0120530.06010.080.072 0.1070.58
1003003004004002.02.557.067.5148030.0470.0640.071 0.0960.52
4 Core1003003011051.5*0.60.99.013.542312.115.4280.10415.42810.2
1003004011051.5*0.60.910.014.852212.115.4280.10415.4289.5
1003004012052.5*0.70.911.516.06187.419.4480.101 9.4487.7
1003004000044*0.70.913.017.87254.615.8780.099 5.8786.8
1003004000066*0.71.2514.520.09853.083.9270.094 3.9254.3
10030040001010*0.71.2516.522.012551.832.3330.093 2.3353.7
100300400016160.71.2519.024.516351.151.4660.088 1.4693.2
100300400025250.91.622.028.521450.7270.9270.082 0.932.3
100300400035350.91.624.531.526450.5240.6680.077 0.673 2
100300400050501.01.626.033.231030.3870.4940.076 0.51.8
100300400070701.12.030.539.244050.2680.3420.075 0.3491.2
100300400095951.12.034.543.256530.1930.2470.074 0.2581.1
1003004001201201.22.538.548.672520.1530.1960.072 0.2090.76
1003004001501501.42.542.553.085530.1240.160.073 0.1760.68
1003004001851851.62.547.558.0103040.09910.1280.073 0.1480.61
1003004002402401.72.553.564.5128950.07540.0990.072 0.1220.54
1003004003003001.82.559.070.3155450.06010.080.072 0.1070.49
1003004004004002.03.1566.579.8202450.0470.0640.071 0.0960.35