- Home
- RR Kabel
- Fire Resistance Cables
- Single Core Fire Resistant
SINGLE CORE FIRE RESISTANT
Applications :-
- These cables are designed for installations in trunking and conduits where a fire situation may pose a major hazard. Circuit integrity is maintained and to achieve optimum performance such cables should be installed in metal conduits.
Specifications :-
- Voltage Rating : 450 / 750 V
- Temperature Range : -20OC to + 90OC (the cable should not be flexed when the temperature is below 0OC)
- Minimum Bending Radius : 8 x Overall diameter
Cable Construction :-
- Conductors : Stranded Cl. 2 plain annealed copper
- Insulation : Mica (fire resistant) tape covered by an extruded layer of cross – linked zero halogen, low smoke insulating compound
Cable Design Parameters :-
- Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required : 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green / yellow, 09 – brown, 12 – grey.
Part Number | Nominal CrossSectional Area (Sq. mm) | Insulation Thickness (mm) | Max. Overall Diameter (mm) | Approx. Cable Weight (kg/km) |
---|
10040101xx60 | 1.5 | 0.7 | 3.8 | 32 |
10040102xx60 | 3 | 0.8 | 4.5 | 43 |
10040103xx60 | 4 | 0.8 | 5.0 | 55 |
10040104xx60 | 6 | 0.8 | 5.5 | 85 |
10040105xx60 | 10 | 1.0 | 7.0 | 146 |
10040106xx60 | 16 | 1.0 | 8.0 | 198 |
10040107xx60 | 25 | 1.2 | 9.7 | 320 |
10040108xx60 | 35 | 1.2 | 10.8 | 410 |
10040109xx60 | 50 | 1.4 | 13.3 | 549 |
10040110xx60 | 70 | 1.4 | 15.1 | 770 |
10040111xx60 | 95 | 1.6 | 17.5 | 1140 |
10040112xx60 | 120 | 1.6 | 19.2 | 1425 |
10040113xx60 | 150 | 1.8 | 21.2 | 1720 |
10040114xx60 | 185 | 2.0 | 23.6 | 2155 |
We are committed to providing the best quality of service