Our Products

Tri Rated Cable

Applications :-
  • These cables are used for internal wiring of panels and electrical equipment. These are used as connection wire in machines laid in protective tubes and flexible pipes and also for motors and transformers.
Technical Data :-
  • Standard : UL 1015, 758, CSA C 22.2 No 210 & BS 6231
  • NominalVoltage : 600V, UL – Type AWM 105°C 600V, CSA – Type AWM 105°C 600V, BS 6231 CK type 90°C 600V
  • TestVoltage (Spark test) AWG 24 : 4kV AWG 22 and 20 : 5kV AWG 18 to 16 : 6kV ≥ AWG 8: 7.5kV
  • Bending Radius : Cable diameter ≤ 8 mm : 4 x outer diameter, Approx diameter > 8 to 12 mm : 5 x outer diameter, Approx diameter > 12 mm : 6 x outer diameter
Cable Design Parameters :-
  • Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 -Violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey, 13 – light blue
Part NumberAWG No.No. of Cores & Nominal Cross Sectional Area (Sq. mm)Approx. Cable Diameter (mm)Approx. Copper Weight (kg/km)Approx Cable Weight (kg/km)
06010101xx30211 x 0.52.64.111
06010102xx30191 x 0.752.86.113.5
06010103xx30181 x 12.98.116
06010104xx30161 x 1.53.211.721
06010105xx30141 x 2.53.619.531
06010106xx30121 x 44.131.545
06010107xx30101 x 64.747.163
06010108xx3081 x 106.381.6111
06010109xx3061 x 168.3131.8183
06010110xx3041 x 259.6204.8267
06010111xx3021 x 3510.8299.7374
06010112xx3011 x 5013.2416.8531
06010113xx302/01 x 7014.9597.2733
06010114xx303/01 x 9516.4774928
06010115xx304/01 x 120189801156
06010116xx30250 kcmil1 x 15020.31208.11439
06010117xx30350 kcmil1 x 18522.41568.21834
06010118xx30450 kcmil1 x 24024.72018.22324